EasyManuals Logo
Home>Siemens>Accessories>SIWAREX WT241

Siemens SIWAREX WT241 User Manual

Siemens SIWAREX WT241
185 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #132 background imageLoading...
Page #132 background image
Communication
11.10 DR 7 Process interfaces
SIWAREX WT241
132 Manual, 05/2015, A5E36046748A
Value
Response
0
Trace recording runs as circulating memory
1
Trace is stopped when the trace memory is full
11.10.14 Load per pulse
By parameterizing the corresponding digital output you can use one of the digital outputs as
a pulse sensor/quantity (see Assignment digital output DQ 0, 1, 2, 3 (Page 128)).
In addition you must specify a load per pulse and a pulse duration for the signal. If the
material flow rate is displayed e.g. in t/h, you must specify the quantity per pulse in t, or with
kg/h in kg. The pulse duration is defined in ms.
Make sure when setting the parameters that you only enter plausible combinations → pulse
duration > (amount per pulse / material flow rate)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIWAREX WT241 and is the answer not in the manual?

Siemens SIWAREX WT241 Specifications

General IconGeneral
BrandSiemens
ModelSIWAREX WT241
CategoryAccessories
LanguageEnglish

Related product manuals