Communication
11.15 DR 13 RS485 parameters
SIWAREX WT241
Manual, 05/2015, A5E36046748Aa 141
Variable
Note
Type
L
Rw
Default
Min.
Max.
Register
RS485
number of
data bits
(Page 142)
Number of
data bits
per charac-
ter
0: 7 data
bits
1: 8 data
bits
BIT
0
rw
0
0
1
1564.15
RS485
number of
stop bits
(Page 142)
Number of
stop bits
0: 1 stop bit
1: 2 stop
bits
BIT
0
rw
0
0
1
1564.14
Bit 3
Reserve
BIT
0
rw
0
0
1
1564.13
Bit 4
Reserve
BIT
0
rw
0
0
1
1564.12
Bit 5
Reserve
BIT
0
rw
0
0
1
1564.11
Bit 6
Reserve
BIT
0
rw
0
0
1
1564.10
Bit 7
Reserve
BIT
0
rw
0
0
1
1564.9
Bit 8
Reserve
BIT
0
rw
0
0
1
1564.8
Bit 9
Reserve
BIT
0
rw
0
0
1
1564.7
Bit 10
Reserve
BIT
0
rw
0
0
1
1564.6
Bit 11
Reserve
BIT
0
rw
0
0
1
1564.5
Bit 12
Reserve
BIT
0
rw
0
0
1
1564.4
Bit 13
Reserve
BIT
0
rw
0
0
1
1564.3
Bit 14
Reserve
BIT
0
rw
0
0
1
1564.2
Bit 15
Reserve
BIT
2
rw
0
0
1
1564.1
RS485
Modbus
address
(Page 142)
MODBUS
address
USHORT
2
rw
20
1
255
1565
Reserve
SHORT
2
rw
0
-
-
1566
Modbus
RTU re-
sponse
delay
(Page 143)
Delay time
for re-
sponse with
MODBUS
RTU in ms
(RS485)
USHORT
2
rw
0
-
-
1567
Reserve
Reserve
FLOAT
4
rw
0
-
-
1568
11.15.1 RS485 protocol
This parameter defines the protocol for communication via the RS485 interface.
Value
Protocol
0
No communication/protocol
1
Modbus RTU

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIWAREX WT241 and is the answer not in the manual?

Siemens SIWAREX WT241 Specifications

General IconGeneral
BrandSiemens
ModelSIWAREX WT241
CategoryAccessories
LanguageEnglish

Related product manuals