EasyManuals Logo

Siemens Synco OZW772 Series User Manual

Siemens Synco OZW772 Series
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #124 background imageLoading...
Page #124 background image
124 / 176
Siemens Web server OZW772... V6.0 CE1C5701en
Building Technologies Trend functions 2015-10-12
9.2.2 Restriction to bus load
Bus load by the trend function is restricted to 1 data point per second
(corresponding to 100 %). The sum of the loads of all 5 trend channels cannot
exceed this value.
No new trends can be started once the value is reached.
In the example below, the query interval of the outside temperature of 1 second
already results in a bus load of 100 %. As a consequence, an additional query of
the room temperature at 50 % load can no longer be started.
Any attempt to start this trend results in a warning.
9.2.3 Reset trend definition
Trends can be reset to the default settings.
The default settings for the values are as follows:
Interval = 15 Min
Number of data points = 0
Status = Invalid
History window = ? days
Bus load = 0 %
Trend name = ""
Any associated trend data is deleted when the trend definition is reset.
1. Click the red waste can symbol
The confirmation window Delete of the trend data opens.
2.
Confirm delete of trend data with OK.
The trend settings and data is deleted.
Note
Procedure

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Synco OZW772 Series and is the answer not in the manual?

Siemens Synco OZW772 Series Specifications

General IconGeneral
BrandSiemens
ModelSynco OZW772 Series
CategoryServer
LanguageEnglish

Related product manuals