Siemens Web server OZW772... V6.0 CE1C5701en
Building Technologies Commissioning 2015-10-12
Path: Home > 0.2.150 OZW772.xx > Settings > Consumption data > Receiver >
E-mail receiver 1…2
· The settings configure sending the consumption data file per e-mail.
· The e-mail signature (sender name, address, etc.) is set under "Settings >
Communication > E-mail".
· The settings are independent of the settings for the message receiver (Section
Message receiver 1…4).
Data point
Explanation, example
E-mail address
Default val: mailReceiver
@example.com
Setting val: max. 49 characters
The setting must match the consumption data
receivers e-mail address.
Transmit interval
Default val: Never
Setting val: Never, daily,
weekly, monthly
The send interval sets how often consumption
data is sent to the e-mail receiver. The setting
"Never" corresponds to "turned off".
File format
Default val: .xml
Setting val: (empty), .xml, .csv
The file format sets the format of the e-mail
attached for consumption data. Two files are
attached if both formats are selected. No file is
added is the setting is empty.
Test receiver
Default val: ---
Setting val: ---, Trigger
"Test receiver" tests the connected to the
selected receiver.
On send interval:
· It is generally sent as soon as the data collection is completed for the Web
Server.
· Daily means between 5 and 10 am.
· Weekly means Sundays (between 5 and 10 am).
· Monthly refers to the third day of the month (between 5 am and 10 pm).
In the case of "Annual allocation", "monthly" can be selected: The 11 additional
e-mails with attached consumption data files are available for backup purposes
or to provide precise billing by the month in the event of a change of renters.
2.5.3.7 Energy indicator
The menu "Energy indicator" is displayed if the controller is connected to the Web
Server that supports the Energy indicator. The menu is hidden if no devices of this
type are connected.
2 e-mail receivers can be defined for the Energy indicator. Settings are made at:
Path: Home > 0.2.150 OZW772.xx > > Settings > Energy indicator
The descriptions are available in Section 7.5 "E-mail with "Energy indicator" for the
plant".
Visibility of the "Energy indicator" can be defined:
Path: Home > 0.2.150 OZW772.xx > Settings > Energy indicator
The descriptions are available in Section 7.2.5 "Energy indicator" visibility".
Receiver
Notes
Notes
E-Mail receiver 1…2
Visibility

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Synco OZW772 Series and is the answer not in the manual?

Siemens Synco OZW772 Series Specifications

General IconGeneral
BrandSiemens
ModelSynco OZW772 Series
CategoryServer
LanguageEnglish

Related product manuals