Siemens Web server OZW772... V6.0 CE1C5701en
Building Technologies Commissioning 2015-10-12
2.2.2 Log into Web Server
A PC with USB interface and web browser is used to commission the Web Server.
1. Start web browser.
2. In the address line, enter the USB IP address (192.168.250.1).
3. First time Login
· User name Administrator
· Password to V5.2(Password): Password
· Password as of V6.0 (Password): Password.1
4. Click [ Login ] to finish.
5. After logging on the first time, the dialog box is displayed to define a new
password.
·
· A new password must be defined the first time you log in (you can also
change the language).
· You cannot exit the dialog box if you do not define a new password (i.e. not
equal to "Password or Password.1") and the following note is displayed:
· The following message is displayed if you fail to fill out all required fields:
Log on
Important note