108 RT-SVP04F-EN
SERVICE MODE Menu (Local Human Interface only)
The SERVICE MODE menu is used to input operating parameters for unit operation
during a service test. Depending on the particular test being conducted, the user will
cycle through all unit outputs (compressors, fans, dampers, heaters, etc.) and
selectively turn them On or Off for the test. After designating the operating status for
each unit component, the operator will designate the “TEST START” delay time.
When a service mode screen is displayed for 30 minutes without a key being pressed,
the LCD screen will revert to the general operating status display. If this happens, press
the SERVICE MODE key again to return to the service menu.
Note: Many of the screens displayed in this section are applicable only for the options
that are installed in the unit and may not be visible on your unit.
To operate the system in the TEST MODE, press the SERVICE MODE key to enter into
the service mode menu and scroll through all of the system outputs and selectively turn
them “On” or “Off.
System Testing & Troubleshooting
Supply Air Controls
Supply Fan OFF
Used With: All Units without IGV/
VFD without Return Fan
Possible Values: ON, OFF, AUTO
OR
Supply Air Controls Used With: All Units when IGV/VFD
is installed without Return Fan
Possible Values: ON, OFF, AUTO
IGV/VFD Cond: 0 - 100%
Supply Fan OFF IGV/VFD Cmd 35%
OR
Supply Fan OFF IGV/VFD Cmd 0% Used With: All units with Return
Fan installed.
Possible Values: Supply Fan= OFF,
ON, AUTO
IGV/VFD= 0-100%
Return Fan= OFF, ON, AUTO
VFD Cmd= 0-100%
Note: IGV/VFD command must be
100% if 2 stage gas is being
tested.
Return Fan OFF VFD Cmd 0%
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
Note: Supply Fan and Return Fan modifications will change a
common SETPOINT (if one is changed, the other
automatically changes.)
RTM VAV Box Relay Used With: All Units
Possible Values: RTM VAV Box
relay, Drive Max Auto, Alarm Output
On/Off
RTM Alarm Output
1. Press the NEXT key until the following screen is displayed.