36 RT-SVP04F-EN
System Operating Status
OUTSIDE AIR VENTILATION STATUS SUBMENU SCREENS
Outside Air Ventilation Status Submenu Used With: All Units with fresh air
configuration set to any option other
than NONE
Press ENTER to View Data in this Submenu
1. Press the NEXT key until the following screen is displayed.
Demand Control Ventilation is ENABLED Used With: All Units
Possible Values: ENABLED,
DISABLED; Space CO
2
Level= 50 to
2200 PPM
Space CO
2
Level: 600 PPM
1. Press the NEXT key until the following screen is displayed.
Note: "Space CO
2
Level" is shown only if "Demand Control
ventilation" is ENABLED
DCV Min OA Flow Target: 80.5 CCFM Used With: All units with Fresh Air
Measurement w/DCV (VCM)
installed and Demand Control
Ventilation Enabled
Possible Values: 0 to 65546 CCFM;
Deadband= 5.0 to 200 CCFM
Deadband: 5.0 CCFM OA Flow XXX CCFM
OR
Active Min OA Flow SETPOINT: 1400 CCFM Used With: All units with Fresh Air
Measurement w/DCV (VCM)
installed and Demand Control
Ventilation Disabled
Possible Values: 0 to 65546 CCFM;
Deadband= 5.0 to 200 CCFM
Deadband: 6.8 CCFM OA Flow XXX CCFM
1. Press the NEXT key until the following screen is displayed.
Outside Air Flow Total: 0 CCFM Used With: All units with Fresh Air
Measurement w/DCV (VCM)
installed.
Possible Values: 0 to 65546 CFM
Front: 0 CCFM Back: 0 CCFM
1. Press the NEXT key until the following screen is displayed.
Outside Air Damper Target: 27% Used With: All units where Fresh
Air Configuration is set to any option
other than NONE.
Possible Values: 0 to 100%
Outside Air Damper Position: 24%
1. Press the NEXT key until the following screen is displayed.
VCM Preheater Output Control: OFF Used With: All units with Fresh Air
Measurement w/DCV (VCM) or OA
Damper Min Position w/DCV (VCM)
installed and Preheat enabled.
Possible Values: VCM Module=
-40.0 to 200.0ºF
VCM Module Aux Temp Input: 47.2ºF
1. Press the NEXT key until the following screen is displayed.