68 RT-SVP04F-EN
System Programming SETUP
PRESSURIZE
Supply Fan - On
Inlet Vanes - Open (if equipped)
Return Fan VFD - Min
Return Fan/Exhaust Damper - Off/Closed (if equipped)
OA Dampers - Open
Heat - All heat stages Off (staged gas and elec.), Hydronic heat & Mod Gas Heat output
at 0%.
Occupied/Unoccupied output - Energized
VO Relay - Energized (with VOM module installed)
VCM Preheater State - Off (with VCM installed)
DEPRESSURIZE
Supply Fan - Off
Inlet Vanes - Closed (if equipped)
Return Fan VFD - Max
Return Fan/Exhaust Damper - On/Open (if equipped)
OA Dampers - Closed
Heat - All heat stages Off (staged gas and elec.), Hydronic heat & Mod Gas Heat output
at 0%.
Occupied/Unoccupied output - De-energized
VO Relay - Energized (with VOM module installed)
VCM Preheater State - Off (with VCM installed)
PURGE
Supply Fan - On
Inlet Vanes - Open (if equipped)
Return Fan/Exhaust Damper - On/Open (if equipped)
Return Fan VFD - Max
OA Dampers - Open
Heat - All heat stages Off (staged gas and elec.), Hydronic heat & Mod Gas Heat output
at 0%.
Occupied/Unoccupied output - Energized
VO Relay - Energized (with VOM module installed)
VCM Preheater State - Off (with VCM installed)
SHUTDOWN
Supply Fan - Off
Inlet Vanes - Closed (if equipped)
Return Fan/Exhaust Damper - Off/Closed (if equipped)
Return Fan VFD - Min
OA Dampers - Closed
Heat - All heat stages Off (staged gas and elec.), Hydronic
heat & Mod Gas Heat output at 0%.
Occupied/Unoccupied output - De-energized
VO Relay - Energized (with VOM module installed)
VCM Preheater State - Off (with VCM installed)