46 RT-SVP04F-EN
System Operating Status
Active Zone Reset Temp Sensor Input From
RTM ZONE TEMP INPUT is 82.0 F
Used With: All Units with Reset
Select not selected as None.
Possible Values: RTM Zone Temp
Input NSB Panel Temp Sensor Input,
RTM Aux Temp Input, Heat Module
Aux Temp Input, ECEM Return Air
Temp Input, BAS/Network Sensor
range: -40 F to 200 F
1. Press the NEXT key until the following screen is displayed.
(if applicable)
Active OA Temperature Sensor Input From
RTM OUTSIDE AIR TEMP INPUT is 86.0 F
Used With: All Units
1. Press the NEXT key until the following screen is displayed. (if
applicable)
Possible Values: RTM Outside Air
Temp Input, BAS/Network
Active Outside Air Humidity Input From
OA HUMIDITY SENSOR INPUT is 30 %
Used With: All Units when an
Economizer is installed
Possible Values: OA Humidity
Sensor Input BAS/Network Sensor
range: 10 to 90%
1. Press the NEXT key until the following screen is displayed. (if applicable)
Active Supply Air Press Input From
RTM SA PRESSURE INPUT is 2.1 IWC
Used With: All units when IGV/VFD
is installed or when the SAP Sensor
is enabled
Possible Values: RTM SA Pressure
Input, BAS/Network; Range: 0 to
7.9 IWC
1. Press the NEXT key until the following screen is displayed. (if applicable)
Active Space Pressure Input From
ECEM SPACE PRESSURE INPUT is 0.08 IWC
Used With: All Units when Power
Exhaust with Statitrac is installed or
Return Fan with Statitrac installed.
Possible Values: ECEM Space
Pressure Input, BAS/Network,
Sensor range: -0.67 to 0.67 IWC
1. Press the NEXT key until the following screen is displayed. (if applicable)
Temp Sensor Input Being Monitored:
RTM ZONE TEMP INPUT is 82.0 F
Used With: All Units
Possible Values: RTM Zone Temp
Input, NSB Panel Temp Sensor
Input, RTM Aux Temp Input, HEAT
Module Aux Temp Input, ECEM
Return Air Temp Input, No Sensor
Selected, Sensor range: -40 F to
200 F
1. Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Enter STATUS
1. Press the NEXT key to leave the submenu and show following screen.
2. Press PREVIOUS to page back through the submenu.
Temperature Input Status Submenu
Press ENTER to View Data in This Submenu
Used With: All Units
1. Pressing the NEXT key will bypass this section.