54 RT-SVP04F-EN
System Programming SETUP
Display Text in: ENGLISH LANGUAGE
Display Units Using: ENGLISH NOTATION
Used With: All Units
Factory Presets: Text and Units :
ENGLISH Language, ENGLISH
Notation
Possible Values: Text : ENG LISH ,
FRENCH, SPANISH
Units: ENGLISH NOTATION, SI
NOTATION
1. Press the + or - key until the proper value is displayed. ENGLISH,
SI
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable).
General Unit Functions Setup Submenu
Press ENTER to Review or Adjust
Used With: All Units
1. Pressing the NEXT key will bypass this section.
If Remote Panel Mode Input Not Present:
System Mode: AUTO
Used With: All Units
1. Press the + or - key until the proper value is displayed. Possible Values: System Mode =
OFF/AUTO
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable).
Reduce Multi-Unit Startup Power Demand
After Power-Up, Delay Unit Start 0 Sec
Used With: All units.
Possible Values: Range 0-255 Sec
(Default 0 Sec)
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
Daytime Warmup Function: ENABLED Used With: All Units when gas,
electric, or hydronic heat is installed.
1. Press the + or - key until the proper value is displayed. Possible Values: ENABLED,
DISABLED
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed. (if
applicable)