RT-SVP04F-EN 91
System Programming SETPOINTS
Derived Zone stp Dead: xx.xF Used With: CV units w/ one stp
only 2.0 -10F DEFAULT 4.0
USED WHEN ONE SETPOINT IS
AVAIL.
1. Pressing the NEXT key will scroll forward through the screens.
Humidity Control SETPOINT Submenu Used With: All units with
Dehumidification or Humidification
option installed.
Press ENTER to Review or Adjust
1. Pressing the NEXT key will bypass this section.
Dehumidify if Space Humidity Above Used With: All IntelliPak units with
Dehumidification option installed
Factory Preset: 60%
Possible Values: 40-65%
Occ Dehumidification Setpoint: 60%
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed (if
applicable)
Stop Dehumid if Space RH Below STP Minus Used With: All IntelliPak units with
Dehumidification option installed
Factory Preset: 5%
Possible Values: 3-10%
Occ Dehumid Hysteresis Offset: 5%
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed (if
applicable)
Dehumidify if Space Humidity Above Used With: All IntelliPak units with
Dehumidification option installed
Factory Preset: 60%
Possible Values: 40-65%
Unocc Dehumidification Setpoint: 60%
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed (if
applicable)
Stop Dehumid if Space RH Below STP Minus Used With: All IntelliPak units with
Dehumidification option installed
Factory Preset: 5%
Possible Values: 3-10%
Unocc Dehumid Hysteresis Offset: 5%
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed (if
applicable)