92 RT-SVP04F-EN
System Programming SETPOINTS
Default Supply Air Reheat Stpt: 70°F Used With: All IntelliPak units with
Dehumidification option installed
Factory Preset: Reheat Setpoint:
70 F; Reheat Deadband: 4 F
Possible Values: Reheat Setpoint:
60-80 F; Reheat Deadband: 2-10 F
Supply Air Reheat Deadband: 4°F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
In Active Dehumidification Mode, Limit Used With: All IntelliPak units with
Dehumidification option installed
Factory Preset: 85%
Possible Values: 50-85%
Maximum Reheat Valve Position To: 85%
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed (if
applicable)
Dehumid Ovrd High Zone Temp Stpt: 75°F Used With: All IntelliPak units with
Dehumidification option installed
Factory Preset: Ovrd High Temp:
75 F; Ovrd Low Temp: 68 F
Possible Values: Ovrd High Temp:
70-85 F; Ovrd Low Temp: 60-75 F
Dehumid Ovrd Low Zone Temp Stpt: 68°F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
Cond Coil Purge Interval Setpt: 90 Min Used With: All IntelliPak units with
Dehumidification option installed
Factory Preset: 90 Minutes
Possible Values: 60-120 Minutes
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed (if
applicable)
Humidify if Space Humidity Below Used With: All units with Occupied
Humidification option installed.
Factory Preset:
30%
Possible Values: 20-50%
Occ Humidification SETPOINT: 30%
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed (if
applicable)
Stop Humid if Space RH Above STP Plus Used With: All units with Occupied
Humidification option installed.
Factory Preset:
5%
Possible Values: 3-10%
Occ Humid Hysteresis Offset: 5%
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed (if
applicable)