RT-SVP04F-EN 23
General Information
Password Protected Screens
Some of the operating displays on the Human Interface LCD screens and require a
password to change. The following screens display the various programming sections
that require a password in order to view or to modify the preset operating parameters.
The password for each screen is a different series of + (Plus) or - (Minus) key strokes in
a predefined sequence. Shown below are the password protected screens, and the
passwords for accessing them.
The following screens display the various programming sections that require a specific
PASSWORD to be entered by a qualified operator in order to modify the operating
parameters. The following screen will appear if the PASSWORD is not entered within
approximately 15 seconds.
Sump Purge Duration Time
2
60 sec. SETUP
Sump Water Heater Setpoint
2
38 F SETUP
Temperature Input Offset for...
Heat morning warmup 0 deg F SETUP
Return air 0 deg F SETUP
RTM zone temperature 0 deg F SETUP
RTM aux temperature 0 deg F SETUP
Outdoor air 0 deg F SETUP
Ventilation override definition See Definitions SETUP
Note 1. Reference note
1
applies to IntelliPak I units only.
Note 2. Reference note
2
applies to IntelliPak II units only.
Password Entry Time Limit Exceeded
1. Press the NEXT key until the following screen is displayed.
Configuration is Password Protected
Please Enter Password: __________
2. Press the + or - keys in this sequence ( + - - - ) to access this restricted screen.
3. Press the ENTER key to confirm the password and enter the menu.
4. Press the NEXT key until the following screen is displayed.
Ventilation Override Mode _______
Enter Password to Lock Definition:
1. Press the + or - keys in this sequence ( + - - + ) to lock each VO Mode.
2. Press the ENTER key to confirm the password and Lock the definitions.
3. Press the NEXT key until the following screen is displayed.