RT-SVP04F-EN 93
System Programming SETPOINTS
Humidify if Space Humidity Below Used With: All units with
Unoccupied Humidification option
installed.
Factory Preset: 30%
Possible Values: 20-50%
Unocc Humidification SETPOINT: 30%
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed (if
applicable)
Stop Humid if Space RH Above STP Plus Used With: All units with
Unoccupied Humidification option
installed.
Factory Preset:
5%
Possible Values: 3-10%
Unocc Humid Hysteresis Offset: 5%
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed (if
applicable)
Used With: All units Screen shown
if in this submenu
End Of Submenu (NEXT) to Enter SETPOINT
1. Press the NEXT key to leave the submenu and show following
screen.
2. Press PREVIOUS to page back through the submenu.
Outside Air Control SETPOINT(S) Submenu Used With: All units with Fresh Air
Configuration set to any option other
than NONE.
Press ENTER to Review or Adjust
1. Pressing the NEXT key will bypass this section.
WHEN ECON COOL, SPACE REDUCE ZONE TEMP COOL STP BY
X.Xf 0-3.0 DEFAULT 1.5
1. Pressing the NEXT key will scroll forward through the screens.
Reference Enthalpy: Enable Air econ Used With: All Units when an
economizer is installed and
Reference Enthalpy is engaged
Factory Presets: 25 BTU/LB
Possible Values: 19 to 28 BTU/LB
Note: This Setpoint is used when
comparative enthaltpy is
not installed or is invalid.
When OA Enthalpy is below: 25 BTU/LB
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Default Econ Drybulb Enable SETPOINT Used With: All units when an
economizer is installed and Dry bulb
Control is enabled--Configuration
set to any option other than NONE.
Possible Values: 50-140º F
(Default 75º F)
Note: This Setpoint is used when
comparative enthaltpy is
not installed or is invalid.
Enable Economizer Below: 75º F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed (if
applicable)