RT-SVP04F-EN 77
System Programming SETUP
Assignment Submenu - VOM Alarms Used With: All units. (if "Any Active
Diagnostic" NO is selected above)
Press ENTER to Review or Adjust
1. Pressing the NEXT key will bypass this section.
Assign Diagnostic to Alarm Output? Used With: All units with VOM
installed. (if ENTER pressed above)
Possible values: YES/NO; VOM
Communications Failure, Ventilation
Override Mode A, Ventilation
Override Mode B, Ventilation
Override Mode C, Ventilation
Override Mode D, Ventilation
Override Mode E
_________________________ YES
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
Assignment Submenu - VCM Alarms Used With: All units. (if "Any Active
Diagnostic" NO is selected above)
Press ENTER to Review or Adjust
1. Pressing the NEXT key will bypass this section.
Assign Diagnostic to Alarm Output? Used With: All units with VCM
installed. (if ENTER pressed above)
Possible values: YES/NO; CO
2
Sensor Failure, VCM Aux Temp
Sensor Failure, Blocked Return Air,
Velocity Pressure Sensor Fail (Back),
VCM Communications Failure,
Velocity Pressure Sensor Fail (Front)
_________________________ YES
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
Assignment Submenu - GBAS Alarms Used With: All units. (if "Any Active
Diagnostic" NO is selected above)
Press ENTER to Review or Adjust
1. Pressing the NEXT key will bypass this section.
Assign Diagnostic to Alarm Output? Used With: All units with GBAS 0-
5VDC installed. (if ENTER pressed
above)
Possible values: YES/NO
GBAS 0-5VDC Module Comm Failure YES
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).