System Programming SETPOINTS
Humidity Ctrl Stpt Source Select Submenu Used With: All Units
Press ENTER to Review or Adjust
1. Pressing the NEXT key will bypass this section.
For Occ Dehumidification Control, Use Used With: All IntelliPak units with
Dehumidification option installed
and GBAS 0-5Vdc or GBAS 0-10Vdc
installed
Factory Preset: HI (KEYPAD)
SETPOINT Menu
Possible Values: HI (KEYPAD)
SETPOINT Menu, GBAS 0-5VDC
Module, GBAS 0-10VDC Module
Setpoint From: HI(KEYPAD) SETPOINT Menu
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed (if
applicable)
For Unocc Dehumidification Control, Use Used With: All IntelliPak units with
Dehumidification option installed
and GBAS 0-5Vdc or GBAS 0-10Vdc
installed
Factory Preset: HI (KEYPAD)
SETPOINT Menu
Possible Values: HI (KEYPAD)
SETPOINT Menu, GBAS 0-5VDC
Module, GBAS 0-10VDC Module
Setpoint From: HI(KEYPAD) SETPOINT Menu
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed (if
applicable)
For Occ Humidification Control, Use Used With: All units with Occupied
Humidification enabled and GBAS 0-
5VDC or 0-10VDC installed.
Factory Presets: HI (KEYPAD)
SETPOINT Menu
Possible Values: HI (KEYPAD)
SETPOINT MENU, GBAS 0-5VDC
Module, GBAS 0-10VDC Module
SETPOINT From: _____________________
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed (if
applicable)
For Unocc Humidification Control, Use Used With: All units with
Unoccupied Humidification enabled
and GBAS 0-5VDC or 0-10VDC
installed.
Factory Presets: HI (KEYPAD)
SETPOINT Menu
Possible Values: HI (KEYPAD)
SETPOINT MENU, GBAS 0-5VDC
Module, GBAS 0-10VDC Module
SETPOINT From: _____________________
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed (if
applicable)
For Supply Air Reheat Control, Use Used With: All IntelliPak units with
Unoccupied Humidification enabled
and GBAS 0-5VDC or 0-10VDC
installed.
Factory Presets: HI (KEYPAD)
SETPOINT Menu
Possible Values: HI (KEYPAD)
SETPOINT MENU, GBAS 0-5VDC
Module, GBAS 0-10VDC Module
Setpoint From: HI(KEYPAD) SETPOINT Menu
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed (if
applicable)