98 RT-SVP04F-EN
System Programming SETPOINTS
For Unocc Zone Temp Cooling Control, Use Used With: All Units
Factory Presets: HI (KEYPAD)
SETPOINT MENU
Possible Values: HI (KEYPAD)
SETPOINT MENU, ZONE SENSOR
SETPOINT INPUT, NSB PANEL
SETPOINT INPUT, GBAS 0-5 VDC
MODULE, GBAS 0-10VDC Module
SETPOINT From: HI (KEYPAD) SETPOINT MENU
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
For Unocc Zone Temp Heating Control, Use Used With: All Units when Gas,
Electric or Hydronic Heat or external
Heat is installed
Factory Presets: HI (KEYPAD)
SETPOINT MENU
Possible Values: HI (KEYPAD)
SETPOINT MENU, ZONE SENSOR
SETPOINT INPUT, NSB PANEL
SETPOINT INPUT, GBAS 0-5 VDC
MODULE, GBAS 0-10VDC Module
SETPOINT From: HI (KEYPAD) SETPOINT MENU
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
For Morning Warmup Temp Control, Use Used With: All Units when Gas,
Electric or Hydronic Heat is installed
Factory Presets: HI (KEYPAD)
SETPOINT MENU
Possible Values: HI (KEYPAD)
SETPOINT MENU, NSB PANEL
SETPOINT INPUT
GBAS 0-5VDC Module
GBAS 0-10VDC Module
SETPOINT From: HI (KEYPAD) SETPOINT MENU
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
For Economizer Dry Bulb Enable, Use Used With: All units with
Economizer installed.
Factory Presets: HI (Kyepad)
SETPOINT Menu
Possible Values: HI (KEYPAD)
SETPOINT MENU, GBAS 0-5VDC
Module, GBAS 0-10VDC Module
SETPOINT From: HI (Keypad) Setpoint Menu_____________
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
For Default OA Damper Min Position, Use Used With: All Units when an
economizer or VCM is installed and
Remote Min Position Pot or GBAS 0-
5VDC or GBAS 0-10VDC is installed.
Factory Presets: HI (KEYPAD)
SETPOINT MENU
Possible Values: HI (KEYPAD)
SETPOINT MENU, REMOTE MIN POS
POT INPUT, GBAS 0-5VDC Module,
GBAS 0-10VDC Module
SETPOINT From: HI (KEYPAD) SETPOINT MENU
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.