RT-SVP04F-EN 97
System Programming SETPOINTS
For Standby Freeze Avoidance, Open the Used With: All units with Hydronic
Heat installed.
Factory Preset: 0%
Possible Values: 0-100%
Hydronic Heat Valve (s) To: 0%
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
Note: When the active outside air
temperature drops below 45
F, this output is active.
Frost Avoidance ON When LRE Temp Below Used With: All units with Energy
Recovery option installed
Factory Preset: 27 F
Possible Values: 0-60 F
Recovery Frost Avoidance Setpoint: 27°F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed (if
applicable)
SETPOINT Source Selections Submenu Used With: All Units
Press ENTER to Review or Adjust
1. Pressing the NEXT key will bypass this section
For Supply Air Temp Cooling Control, Use Used With: All Units
Factory Presets: HI (Keypad)
Setpoint Menu
Possible Values: HI (KEYPAD)
SETPOINT MENU, ZONE SENSOR
SETPOINT INPUT, NSB PANEL
SETPOINT INPUT, GBAS 0-5 VDC
MODULE, GBAS 0-10VDC Module‘
SETPOINT From: HI (KEYPAD) SETPOINT MENU
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
For Supply Air Temp Heating Control, Use Used With: All Units when hydronic
Heat or Modulating Gas Heat is
installed with GBAS 0-5VDC or GBAS
0-10 VDC module
Factory Presets: HI (Keypad)
Setpoint Menu
Possible Values: HI (KEYPAD)
SETPOINT MENU, GBAS 0-5VDC
Module, GBAS 0-10VDC Module
SETPOINT From: HI (KEYPAD) SETPOINT MENU
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
For Occ Zone Temp Heating Control, Use Used With: All Units when Gas,
Electric or Hydronic Heat is installed
with Daytime Warmup Enabled
Factory Presets: HI (KEYPAD)
SETPOINT MENU
Possible Values: HI (KEYPAD)
SETPOINT MENU, ZONE SENSOR
SETPOINT INPUT, NSB PANEL
SETPOINT INPUT, GBAS 0-5 VDC
MODULE, GBAS 0-10VDC Module
SETPOINT From: HI (KEYPAD) SETPOINT MENU
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.