96 RT-SVP04F-EN
System Programming SETPOINTS
Default Supply Air Pressure: 2.0 IWC Used With: All Units when IGV/VFD
is installed. High Limit shown when
VAV without IGV/VFD & Supply Air
Pressure Sensor is installed.
Factory Presets: SETPOINT: 2.0
IWC
High Limit: 4.0 IWC
Deadband: 0.5 IWC
Possible Values: SETPOINT 0.7 -
5.1 IWC
High Limit 1.2 - 5.7 IWC
Deadband 0.1 - 2.0 IWC
High Limit: 4.0 IWC Deadband: 0.5 IWC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
Note: SETPOINT cannot be
adjusted above: High Limit
= Deadband divided by 2
minus 0.1
Max Return Plenum Pressure Stp: 1.2 IWC Used With: All units with Return
Fan VFD installed.
Possible Values: Max Return= 0.1
- 2.5 IWC (Default 1.2 IWC)
Deadband= 0.1 - 1.0 IWC (default
0.2 IWC)
Deadband: 0.2 IWC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
Default Space Pressure SETPOINT: 0.08 IWC Used With: All Units when Power
Exhaust with Statitrac is installed or
Return Fan with Statitrac installed
Factory Presets: SETPOINT: 0.08
IWC, Deadband: 0.04 IWC
Possible Values: SETPOINT: -0.2
to 0.3 IWC, Deadband 0.02 - 0.2
IWC
Space Pressure Deadband: 0.10 IWC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
Exhaust Enable Point. Enable Exhaust Fan Used With: All Units when Power
Exhaust with or without Statitrac
installed, but without Return Fan.
Factory Presets:
25%
Possible Values: 0 to 100%
When Outside Air damper is Above: 25%
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Low Ambient Comp Lockout Temp: 50 F Used With: All Units with DX
Cooling
Factory Presets: 50 F
Possible Values: -20 F to 80 F
Comp(s) OFF if OA Temp Below This Value
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.