RT-SVP04F-EN 95
System Programming SETPOINTS
Default Design Min OA Damper Pos: 15% Used With: All units with DCV
enabled and 0-100% OA Damper
installed.
Possible Values: Default Design=
0-100% (default 15%); Default
DCV= 0-100% (Default 10%)
Default DCV Min OA Damper Pos Stp: 10%
OR
Default OA Damper Min Position: 15% Used With: VAV units with IGV/VFD
and 0-100% OA Damper and OA
CFM Compensation is enabled.
Possible Values: 0-100% (Default
15%)
With IGV/VFD Command At Minimum (0%)
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
Note: OA Damper Min Pos with IGV at Min MUST BE > OA Damper
Min Pos with IGV at Max
Default OA Damper Min Position: 15% Used With: VAV units with IGV/VFD
and 0-100% OA Damper and OA
CFM Compensation is enabled.
Possible Values: 0-100% (Default
10%)
With IGV/VFD Command At Maximum (100%)
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
Note: OA Damper Min Pos with IGV at Min MUST BE > OA Damper
Min Pos with IGV at Max
OR
Default OA Damper Min Position: 15% Used With: Screen shown only if
0-25% Damper installed, or unit is
configured with 0-100% Damper
with DCV disabled and OA CFM
Compensation function disabled.
Possible Values: 0-100% (Default
15%)
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
Note: If unit has TRAQ, this
setpoint is not used.
Used With: All units
End Of Submenu (NEXT) To Enter SETPOINT
1. Press the NEXT key to leave the submenu and show following
screen.
2. Press PREVIOUS to page back through the submenu.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane IntelliPak I and is the answer not in the manual?

Trane IntelliPak I Specifications

General IconGeneral
BrandTrane
ModelIntelliPak I
CategoryAir Conditioner
LanguageEnglish

Related product manuals