RT-SVP04F-EN 89
SETPOINT Menu
The SETPOINT menu is used to designate default zone temperature SETPOINTs, supply
air and space pressure SETPOINTs, and low ambient compressor lockout SETPOINTs.
These SETPOINTs will be active (in use) for the “SETPOINT Source Selection”
designated as “DEFAULT” for these inputs.
When a SETPOINT screen is displayed for 30 minutes without a key being pressed, the
LCD screen will revert to the general operating status display. If this happens, press the
SETPOINT key again to return to the SETPOINT menu.
Note: Many of the screens displayed in this section are applicable only for the options
that are installed in the unit and may not be visible on your unit.
Press the SETPOINT key to begin viewing or modifying the unit SETPOINTs.
System Programming SETPOINTS
Default Supply Air Temp SETPOINT Used With: All Units
Factory Presets: 55 F
Possible Values: 40 F to 90 F
Cooling: 55 F
OR
Default Supply Air Temp SETPOINTS Used With: All Units with Hydronic,
Electric, or Modulating Gas Heat.
Factory Presets:
Heating: 100 F,
Cooling: 55 F
Possible Values: Cool: 40 F to 90
F, Heat: 40 F to 180 F
Cooling: 55 F Heating: 100 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
Supply Air Temperature Deadband Used With: All Units
Factory Presets: 8.0 F
Possible Values: Cooling: 4 - 20 F
Cooling: 8.0 F
OR