74 RT-SVP04F-EN
System Programming SETUP
GBAS (0-10 VDC) Analog Output 1 Assignment
NOT ASSIGNED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
Used with: All units when GBAS 0-
10 VDC Module
Factory Presets: Not Assigned
Possible Values: ACTIVE COOLING
CAPACITY, ACTIVE HEATING
CAPACITY, OUTSIDE AIR
TEMPERATURE, ACTIVE ZONE
TEMPERATURE, ACTIVE SUPPLY AIR
TEMPERATURE, ACTIVE SUPPLY AIR
PRESSURE, ACTIVE SPACE
PRESSURE, ACTIVE SPACE
RELATIVE HUMIDITY, ACTIVE
OUTDOOR AIR RELATIVE HUMIDITY,
ACTIVE SPACE CO
2
LEVEL, ACTIVE
OUTDOOR AIR DAMPER POSITION,
ACTIVE OUTDOOR AIR FLOW
GBAS (0-10 VDC) Analog Output 2 Assignment
NOT ASSIGNED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Press the NEXT key to display Generic BAS Analog Output 3 screen
5. Press the + or - key until the proper value is displayed.
6. Press the ENTER key to confirm each choice.
7. Repeat steps 1-4 to display Generic BAS Analog Output screens 3 &
4.
8. Press the NEXT key to advance to the following screen.
End of Submenu (NEXT) to enter SETUP
1. Press the NEXT key to leave the submenu and show following
screen.
2. Press PREVIOUS to page back through the submenu.
RTM Alarm Output Diagnostic Assignments Used with: All Units
Press ENTER to Review or Adjust
1. Pressing the NEXT key will bypass this section.
RTM Alarm Output Setup Submenu Screen always shown
Press ENTER to Review or Adjust
1. Pressing the ENTER key will allow viewing of this Submenu.
Assign Diagnostic to Alarm Output? Used with: All Units
Possible values: Any Active
Diagnostic (YES), Any Active
Diagnostic (NO)
Note: If (NO) is selected, any or all
of the diagnostics in the
Assignment Submenu--
RTM Alarms may be
assigned.
Any Active Diagnostic ____________________ (YES)
1. Press the ENTER key then the NEXT key to display the possible
diagnostics that may be assigned to the RTM alarm output
definition.
2. Press the + (Plus) key to assign "Yes" to the output definition or -
(Minus) key to assign "No" to the output definition.
3. Press the ENTER key to confirm each selection.
Assignment Submenu - RTM Alarms All units (if "Any Active Diagnostic"
(NO) is selected above)
Press ENTER to Review or Adjust
1. Pressing the NEXT key will bypass this section.