RT-SVP04F-EN 111
System Testing & Troubleshooting
Sump Fill Relay: OFF Used With: All IntelliPak II units
with water-cooled condensers
installed
Factory Preset: OFF
Possible Values: ON, OFF
Sump Drain Relay: OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
Sump Heater Relay: OFF Used With: All IntelliPak II units
with water-cooled condensers and
sump heat installed
Factory Preset: OFF
Possible Values: ON, OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed
(if applicable).
Condenser Fan Outputs (MCM 1) Used With: All Rooftops or Air
Handlers with DX Cooling and
Airside Condensers.
Possible Values: ON, OFF, AUTO
K1 OFF K2 OFF K5 OFF K6 OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
Note: If either 1A or 1B (Ckt 1) is set to AUTO, the other will
automatically be changed to AUTO. The same is true of 2A
and 2B (Ckt 2). If either is set to AUTO, the other will be
changed also
Condenser Fan Speed (MCM) Used With: All Rooftops and Air
Handlers with DX Cooling and
Airside Condensers.
Possible Values: AUTO, 0-100%
(default 0%)
Ckt 1 0% Ckt 2 0%
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).