Planning the electrical installation
62
Note 9: Sine filters protect the motor insulation system. Therefore, du/dt filter can be replaced with a
sine filter. The peak phase-to-phase voltage with the sine filter is approximately 1.5 · U
N
.
Note 10: Common mode filter is available as a plus code option (+E208) or as a separate kit (one box
including three rings for one cable).
Selecting the power cables
General rules
Dimension the input power and motor cables according to local regulations:
Dimension the cable to carry the drive load current. See chapter Technical data
for the rated currents.
Select a cable rated for at least 70
°C maximum permissible temperature of
conductor in continuous use. For US, see Additional US requirements, page 65.
The inductance and impedance of the PE conductor/cable (grounding wire) must
be rated according to permissible touch voltage appearing under fault conditions
(so that the fault point voltage will not rise excessively when a ground fault
occurs).
600 V AC cable is accepted for up to 500 V AC
Use symmetrical shielded motor cable, see page 65. Ground the shield(s) of motor
cable(s) 360° at both ends.
Note: When continuous metal conduit is employed, shielded cable is not required.
The conduit must have bonding at both ends as with cable shield.
Û
LL
/U
N
Without du/dt filter
Cable length (m)
du/dt
U
N
-------------(1/μs)
1.0
2.0
5.0
4.0
3.0
1.5
2.5
3.5
4.5
100 200 300
100 200 300
0.0
0.5
1.0
1.5
2.0
2.5
3.0
Cable length (m)
With du/dt filter
du/dt
U
N
-------------(1/μs)
Û
LL
/U
N
5.5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Table of Contents

Other manuals for ABB ACS850

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS850 and is the answer not in the manual?

ABB ACS850 Specifications

General IconGeneral
SafetySTO (Safe Torque Off)
CommunicationCANopen
EnclosureIP21
Output VoltageUp to 1000 V DC
Protection FeaturesOvercurrent, Overvoltage, Undervoltage
Cooling MethodAir or liquid cooling
Input Voltage380 to 690 V AC

Related product manuals