Parameters 135
11.02 DIO delayed status Displays the delayed status of digital input/outputs
DIO2…DIO1. This word is updated only after
activation/deactivation delays (if any are specified).
Example: 0010 = DIO2 is on, DIO1 is off.
This parameter is read-only.
-
0000b…0011b Delayed status of digital input/outputs. 1 = 1
11.05 DIO1 function Selects whether DIO1 is used as a digital output or input,
or a frequency input.
Output
Output DIO1 is used as a digital output. 0
Input DIO1 is used as a digital input. 1
Frequency DIO1 is used as a frequency input. 2
11.06 DIO1 output source Selects a drive signal to be connected to digital
input/output DIO1 when parameter 11.0 5 DIO1 function is
set to Output.
Ready run
Not energized Output is off. 0
Energized Output is on. 1
Ready run Bit 1 of 06.11 Main status word (see page 117). 2
Enabled Bit 0 of 06.16 Drive status word 1 (see page 117). 4
Started Bit 5 of 06.16 Drive status word 1 (see page 117). 5
Magnetized Bit 1 of 06.17 Drive status word 2 (see page 118). 6
Running Bit 6 of 06.16 Drive status word 1 (see page 117). 7
Ready ref Bit 2 of 06.11 Main status word (see page 117). 8
At setpoint Bit 8 of 06.11 Main status word (see page 117). 9
Reverse Bit 2 of 06.19 Speed control status word (see page 120). 10
Zero speed Bit 0 of 06.19 Speed control status word (see page 120). 11
Above limit Bit 10 of 06.17 Drive status word 2 (see page 118). 12
Warning Bit 7 of 06.11 Main status word (see page
117 ). 13
Fault Bit 3 of 06.11 Main status word (see page 117). 14
Fault (-1) Inverted bit 3 of 06.11 Main status word (see page 117 ). 15
Open brake
command
Bit 0 of 44.01 Brake control status.
(See ACS880 primary control program firmware manual
(3AUA0000085967[English])).
22
Ext2 active Bit 11 of 06.16 Drive status word 1 (see page 117). 23
Remote control Bit 9 of 06.11 Main status word (see page 117). 24
Supervision 1 Bit 0 of 32.01 Supervision status (see page 251). 33
Supervision 2 Bit 1 of 32.01 Supervision status (see page 251). 34
Supervision 3 Bit 2 of 32.01 Supervision status (see page 251). 35
RO/DIO control word
bit0
Bit 0 of 10.99 RO/DIO control word (see page 134). 40
RO/DIO control word
bit1
Bit 1 of 10.99 RO/DIO control word (see page 134). 41
RO/DIO control word
bit2
Bit 2 of 10.99 RO/DIO control word (see page 134). 42
No. Name/Value Description Def/
FbEq16

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS880 PCP and is the answer not in the manual?

ABB ACS880 PCP Specifications

General IconGeneral
Output currentUp to 5200 A
Input voltage380-690 V
Power range5600 kW
Cooling methodAir or liquid
Protection classIP21, IP54
Communication interfacesEthernet, CANopen

Related product manuals