Parameters 279
45.09 CO2 reduction in tons Displays the reduction in CO
2
emissions in metric tons
compared to direct-on-line motor connection. This value is
calculated by multiplying the saved energy in MWh by the
value of parameter 45.18 CO2 conversion factor (by
default, 0.5 metric tons/MWh).
When this parameter rolls over, parameter 45.08 CO2
reduction in kilotons is incremented.
This parameter is read-only (see parameter 45.21 Energy
calculations reset).
-
0.0…999.9 metric
tons
Reduction in CO
2
emissions in metric tons. 1 = 1 metric
ton
45.11 Energy optimizer Enables/disables the energy optimization function. The
function optimizes the motor flux so that total energy
consumption and motor noise level are reduced when the
drive operates below the nominal load. The total efficiency
(motor and drive) can be improved by 1…20% depending
on load torque and speed.
Note: With a permanent magnet motor or a synchronous
reluctance motor, energy optimization is always enabled
regardless of this parameter.
Disable
Disable Energy optimization disabled. 0
Enable Energy optimization enabled. 1
45.12 Energy tariff 1 Defines energy tariff 1 (price of energy per kWh).
Depending on the setting of parameter 45.14 Tariff
selection, either this value or 45.13 Energy tariff 2 is used
for reference when monetary savings are calculated.
The currency is defined by parameter 45.17 Tariff currency
unit.
Note: Tariffs are read only at the instant of selection, and
are not applied retroactively.
1.000 units
0.000…4294966.296
units
Energy tariff 1. -
45.13 Energy tariff 2 Defines energy tariff 2 (price of energy per kWh).
See parameter 45.12 Energy tariff 1.
2.000 units
0.000…4294966.296
units
Energy tariff 2. -
45.14 Tariff selection Selects (or defines a source that selects) which pre-
defined energy tariff is used.
0 = 45.12 Energy tariff 1
1 = 45.13 Energy tariff 2
Energy tariff 1
Energy tariff 1 0. 0
Energy tariff 2 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
DIO1 Digital input/output DIO1 (11 .02 DIO delayed status, bit 0). 10
DIO2 Digital input/output DIO2 (11 .02
DIO delayed status, bit 1). 11
No. Name/Value Description Def/
FbEq16

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS880 PCP and is the answer not in the manual?

ABB ACS880 PCP Specifications

General IconGeneral
Output currentUp to 5200 A
Input voltage380-690 V
Power range5600 kW
Cooling methodAir or liquid
Protection classIP21, IP54
Communication interfacesEthernet, CANopen

Related product manuals