356 Parameters
99.11 Motor nominal cos Φ Defines the cosphi of the motor for a more accurate motor
model. The value is not obligatory, but is useful with an
asynchronous motor, especially when performing a
standstill identification run. The setting should match the
value on the rating plate of the motor.
With a permanent magnet or synchronous reluctance
motor, this value is not needed.
Note: This parameter cannot be changed while the drive is
running.
0.00
0.00…1.00 Cosphi of the motor. 100 = 1
99.12 Motor nominal torque Defines the nominal motor shaft torque. This value can be
given instead of nominal power (99.10) if shown on the
rating plate of the motor.
The unit is selected by parameter 96.16 Unit selection.
Note:
• This setting is an alternative to the nominal power value
(99.10). If both are entered, 99.12 takes priority.
• This parameter cannot be changed while the drive is
running.
0.000
N·m or lb·ft
0.000…4000000.000
N·m or lb·ft
Nominal motor torque. 1 = 1 unit
99.13 ID run requested Selects the type of the motor identification routine (ID run)
performed at the next start of the drive. During the ID run,
the drive will identify the characteristics of the motor for
optimum motor control.
If no ID run has been performed yet (or if default
parameter values have been restored using parameter
96.06 Parameter restore), this parameter is automatically
set to Standstill, signifying that an ID run must be
performed.
After the ID run, the drive stops and this parameter is
automatically set to None.
Note:
• For the Advanced ID run, the machinery must always
be de-coupled from the motor.
• With a permanent magnet or synchronous reluctance
motor, a Normal, Reduced or Standstill ID run requires
that the motor shaft is NOT locked and the load torque
is less than 10%.
• With scalar control mode (99.04 Motor ctrl mode =
Scalar), only the Current measurement calibration ID
run mode is possible.
• Once the ID run is activated, it can be canceled by
stopping the drive.
• The ID run must be performed every time any of the
motor parameters (99.04, 99.06…99.12) have been
changed.
• Ensure that the Safe torque off and emergency stop
circuits (if any) are closed during the ID run.
• Mechanical brake (if present) is not opened by the logic
for the ID run.
• This parameter cannot be changed while the drive is
running.
None
None No motor ID run is requested. This mode can be selected
only if the ID run (
Normal, Reduced, Standstill, Advanced,
Advanced Standstill) has already been performed once.
0
No. Name/Value Description Def/
FbEq16

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS880 PCP and is the answer not in the manual?

ABB ACS880 PCP Specifications

General IconGeneral
Output currentUp to 5200 A
Input voltage380-690 V
Power range5600 kW
Cooling methodAir or liquid
Protection classIP21, IP54
Communication interfacesEthernet, CANopen

Related product manuals