434 Fault tracing
FB11 Memory unit missing No memory unit is attached to
the control unit.
Power down the control unit.
Check that the memory unit is
properly inserted into the control
unit.
The memory unit attached to
the control unit is empty.
Power down the control unit. Attach
a memory unit (with the appropriate
firmware) to the control unit.
FB12 Memory unit incompatible The memory unit attached to
the control unit is
incompatible.
Power down the control unit.
Attach a compatible memory unit.
FB13 Memory unit FW
incompatible
The firmware on the attached
memory unit is incompatible
with the drive.
Power down the control unit.
Attach a memory unit with
compatible firmware.
FB14 Memory unit FW load
failed
The firmware on the attached
memory unit could not be
loaded to the drive.
Power down the control unit.
Check that the memory unit is
properly inserted into the control
unit.
If the problem persists, replace the
memory unit.
FF61 ID run Motor ID run was not
completed successfully.
Check the nominal motor values in
parameter group 99 Motor data.
Check that no external control
system is connected to the drive.
Cycle the power to the drive (and
its control unit, if powered
separately).
Check that no operation limits
prevent the completion of the ID
run. Restore parameters to default
settings and try again.
Check that the motor shaft is not
locked.
Check the auxiliary code.
FF81 FB A force trip A fault trip command has
been received through
fieldbus adapter A.
Check the fault information
provided by the PLC.
FF82 FB B force trip A fault trip command has
been received through
fieldbus adapter B.
Check the fault information
provided by the PLC.
FF8E EFB force trip A fault trip command has
been received through the
embedded fieldbus interface.
Check the fault information
provided by the Modbus controller.
D100 Overtemperature fault 09.10 Measured
temperature exceeded 79.08
Fault temperature limit for 3
sec or the Klixon digital input
is false.
Check for problem in measurement
device.
Check for problem in temperature
measurement circuit.
Check well and discharge
pressures (excessive pressure can
cause heating).
Check warning function setting in
parameters.
Code
(hex)
Fault Cause What to do

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS880 PCP and is the answer not in the manual?

ABB ACS880 PCP Specifications

General IconGeneral
Output currentUp to 5200 A
Input voltage380-690 V
Power range5600 kW
Cooling methodAir or liquid
Protection classIP21, IP54
Communication interfacesEthernet, CANopen

Related product manuals