EasyManuals Logo
Home>ABB>Measuring Instruments>CoreSense M10

ABB CoreSense M10 User Manual

ABB CoreSense M10
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
APPENDIX A
Modbus
The RS-485 and Modbus default settings can be modified using the web interface.
NOTICE
For best results it is recommended to configure the Modbus master with a timeout of
10000 ms and 5 retries.
Minimum delay between polls shall be at least 100 ms.
The Modbus slave ID is 1.
RS-485 configuration
Baud rate 9600
Data Bits 8
Stop bits 1
Parity None
Flow control None (only none is supported)
TCP configuration port
Modbus TCP 502/tcp

Table of Contents

Other manuals for ABB CoreSense M10

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB CoreSense M10 and is the answer not in the manual?

ABB CoreSense M10 Specifications

General IconGeneral
BrandABB
ModelCoreSense M10
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals