3.5 Function tests
3.5.1 Function test of emergency stop
Overview
Perform this test on the emergency stop button both on the operating panel and
on the FlexPendant.
Performing the function test
NoteAction
If any damage is found on the emergency
stop button, it must be replaced.
Make a visual inspection of the emergency
stop button to make sure it is not physically
damaged.
1
Start the robot system.2
The test is passed if the event message
“10013 emergency stop state” appears in
the FlexPendant log.
Press the emergency stop button.3
If the event message “10013 emergency
stop state” does not appear or if the event
message “20223 Emergency stop conflict”
appears in the FlexPendant log, the test is
failed and the root cause of the failure must
be found.
After the test, release the emergency stop
button and press the motors on button to
reset the emergency stop state.
4
118 Product manual - IRC5 Compact
3HAC047138-001 Revision: G
© Copyright 2009-2017 ABB. All rights reserved.
3 Maintenance
3.5.1 Function test of emergency stop

Table of Contents

Other manuals for ABB IRC5 Compact

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB IRC5 Compact and is the answer not in the manual?

ABB IRC5 Compact Specifications

General IconGeneral
BrandABB
ModelIRC5 Compact
CategoryController
LanguageEnglish

Related product manuals