Ekip Multimeter module
The Ekip Multimeter is a remote viewing unit on the front of the switchgear and is equipped with a touchscreen
display.
It can be installed in the presence of Ekip Dip, Touch, Hi-Touch, G Touch and G Hi-Touch releases, with which
it communicates via Local Bus. It must be powered independently from the release to which it is connected,
and can be powered in AC at nominal 110… 240 V AC, or DC at nominal 24...48 V DC.
IMPORTANT: AC and DC power supplies cannot be present at the same time.
The Ekip Multimeter is a remote viewing unit on the front of the switchgear and is equipped with a touchscreen
display.
It can be installed in the presence of Ekip Dip, Touch, Hi-Touch, G Touch and G Hi-Touch releases, with which
it communicates via Local Bus. It must be powered independently from the release to which it is connected,
and can be powered in AC at nominal 110… 240 V AC, or DC at nominal 24...48 V DC.
One release can communicate with a maximum of four Ekip Multimeters. On the other hand, the module can
be connected to only one release.
In addition, the module makes an auxiliary voltage of 24 V DC available, which can be used to power the
release. If the release is powered through Ekip Multimeter, the power supply must be applied directly on the
terminal box of the circuit-breaker: in fact the Ekip Multimeter is sized in order to supply only the release, and
therefore it is not able to supply sufficient power to supply an Ekip Supply module and any other electronic
accessories connected to the terminal box.
In the case of connection to an Ekip Touch, Hi-Touch, G-Touch, and G Hi-Touch release, as well as displaying
the measurements, the module also allows you to set parameters and the protection thresholds.
Further information on Ekip Multimeter is available from the web site http://www.abb.com/abblibrary/
DownloadCenter/, in particular in the kit sheet 1SDH001000R0520.
Contacts Ekip AUP
The communication modules are always supplied with dedicated Ekip AUP auxiliary position contacts, which
in the case of a withdrawable circuit-breaker supply the inserted/extracted signal of the moving part from the
fixed part.
The assembly assures that the position signalling is also maintained with the moving part withdrawn.
IMPORTANT: in the presence of multiple communication modules, only one of these
can be connected to the Ekip AUP contacts.
Further information on assembling Ekip AUP modules and contacts is available from the web site http://www.
abb.com/abblibrary/DownloadCenter/, in particular in the kit sheet 1SDH001000R0603.
Ekip RTC contact
The communication modules are always supplied with an Ekip RTC auxiliary contact, which supplies the
release with the signal indicating that the circuit-breaker ready to receive a close command.
Further information on the assembly of the Ekip RTC contact is available from the web site http://www.abb.
com/abblibrary/DownloadCenter/, in particular in the kit sheet 1SDH001000R0604.

Table of Contents

Other manuals for ABB SACE Emax 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB SACE Emax 2 and is the answer not in the manual?

ABB SACE Emax 2 Specifications

General IconGeneral
TypeAir circuit breaker
Rated Current800 A to 6300 A
Breaking CapacityUp to 150 kA at 415 V AC
Frequency50/60 Hz
Number of Poles3, 4
InstallationFixed or withdrawable
StandardsIEC 60947-2
Trip UnitEkip Touch, Ekip Hi-Touch
CommunicationModbus, Profibus, Ethernet