F-4 Troubleshooting
Controller Communication Channel Troubleshooting
Indicator Color Channel Mode Description Probable Cause Recommended Action
A or B Green
(steady)
Remote I/O Scanner Active Remote I/O link, all
adapter modules are
present and not faulted
Normal operation No action required
Remote I/O Adapter Communicating with
scanner
DH+ Controller is transmitting or
receiving on DH+ link
Green
(blinking
rapidly or
slowly)
Remote I/O Scanner At least one adapter is
faulted or has failed
• Power off at
remote rack
• Cable broken
• Restore power to
the rack
• Repair cable
DH+ No other nodes on network
Red
(steady)
Remote I/O Scanner
Remote I/O Adapter
DH+
Hardware fault Hardware error Turn power off, then on
Check that the software
configurations match the
hardware set-up
Replace the controller.
Red
(blinking
rapidly or
slowly)
Remote I/O Scanner All adapters faulted
• Cable not
connected or
broken
• Power off at
remote racks
• Repair cable
• Restore power to racks
DH+ Bad communication on DH+ Duplicate
node detected
Correct station address
Off Remote I/O Scanner
Remote I/O Adapter
DH+
Channel offline Channel is not
being used
Place channel online
if needed

Table of Contents

Other manuals for Allen-Bradley PLC-5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PLC-5 and is the answer not in the manual?

Allen-Bradley PLC-5 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPLC-5
CategoryController
LanguageEnglish

Related product manuals