ID-FLX Lite & Telecom Global Guide
103
Group: Communication settings
Setpoint group
Communication
Settings
Related FW 2.5.0
Range [units] [-]
Default value -
Step -
Comm object 24537 Related applications
Description
It is controller’s identification number. It is possible to set controller address different from the default value 1
so that more ID-Lite controllers can be interconnected (via RS485) and accessed e.g. from Modbus terminal.
Adresses 1 .. 32
Note: When opening connection to the controller its address has to correspond with the setting in PC
tool.
ControllerAddr
6 back to List of setpoints
Setpoint group
Communication
Settings
Related FW 2.5.0
Range [units] [DIRECT / MODEM / MODBUS / ECU LINK]
Default value -
Step -
Comm object 24522 Related applications
Description
Communication protocol switches for the COM1 channel.
DIRECT
LiteEdit communication protocol via direct cable or AirGate, WebSupervisor
communication protocol via AirGate.
MODEM LiteEdit communication protocol via modem.
MODBUS Modbus protocol. See detailed description in InteliDrive Communication Guide.
ECU link Protocol for communication with Cummins engines via Modbus.
Note: For details on communication speed and other technical parameters please see Technical data
on page 87.
For detail description see chapter Modbus protocol.
COM1 Mode
6 back to List of setpoints