InteliLite Global Guide
461
LBI: S
Related FW 1.2.1 Related applications AMF, MRS
Comm object 44
Description
If this input is active, all alarms except Emergency Stop and Overspeed are suppressed. The suppressed
alarms will be displayed in the alarm list, but they will not take effect regarding the gen-set control.
Note: Sd Override (page 461) is indicated in the alarm list if Sd Override mode is active to inform the
operator that the engine is not protected.
IMPORTANT: MISUSE OF THIS INPUT CAN CAUSE DAMAGE TO THE GEN-SET!
Sd Override
6 back to Logical binary inputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 189
Description
Binary input has the same function as Start Button on the InteliLite front panel. It is evaluated in MAN
mode only.
Start Button
6 back to Logical binary inputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 190
Description
Binary input has the same function as Stop Button on the InteliLite front panel. It is evaluated in MAN
Mode only.
Stop Button
6 back to Logical binary inputs alphabetically

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals