EasyManuals Logo
Home>Danfoss>DC Drives>VLT AutomationDrive FC 302

Danfoss VLT AutomationDrive FC 302 Programming Guide

Danfoss VLT AutomationDrive FC 302
722 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #160 background imageLoading...
Page #160 background image
Option
Name
Description
[8]
Select setup 2
[9]
Select setup 3
[10]
Select setup 4
[11]
Stop & trip
Warning 90, Feedback monitor is active as soon as the value in parameter 4-31 Motor Feedback Speed Error is exceeded, regardless of
the setting in parameter 4-32 Motor Feedback Loss Timeout. Warning/Alarm 61, Feedback Error is related to the motor feedback loss
function.
Parameter 4-31 Motor Feedback Speed Error
Table 278: Parameter 4-31 Motor Feedback Speed Error
4-31 Motor Feedback Speed Error
Default value: 300 RPM
Parameter type: Range, 1 - 600 RPM
Setup: All setups
Conversion index: 67
Data type: Uint16
Change during operation: True
Select the minimum allowed error in speed (output speed vs. feedback).
Time
[sec]
Speed
[rpm]
n
calc
n
actual
P 4-32
e30ba221.11
P 4-31
Illustration 57: Motor Feedback Speed Error
Parameter 4-32 Motor Feedback Loss Timeout
Table 279: Parameter 4-32 Motor Feedback Loss Timeout
4-32 Motor Feedback Loss Timeout
Default value: Size related
Parameter type: Range, 0 - 60 RPM
Setup: All setups
Conversion index: -2
Data type: Uint16
Change during operation: True
Set the timeout value allowing the speed error set in parameter 4-31 Motor Feedback Speed Error to be exceeded before enabling the
function selected in parameter 4-30 Motor Feedback Loss Function.
AU275636650261en-000101 / 130R0334160 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals