Parameter 6-14 Terminal 53 Low Ref./Feedb. Value
Table 404: Parameter 6-14 Terminal 53 Low Ref./Feedb. Value
6-14 Terminal 53 Low Ref./Feedb. Value
Default value: Size related
Parameter type: Range, -999999.999 - 999999.999 ReferenceFeed-
backUnit
Setup: All setups
Conversion index: -3
Data type: Int32
Change during operation: True
Enter the analog input scaling value that corresponds to the low voltage/low current set in parameter 6-10 Terminal 53 Low Voltage
and parameter 6-12 Terminal 53 Low Current.
Parameter 6-15 Terminal 53 High Ref./Feedb. Value
Table 405: Parameter 6-15 Terminal 53 High Ref./Feedb. Value
6-15 Terminal 53 High Ref./Feedb. Value
Default value: Size related
Parameter type: Range, -999999.999 - 999999.999 ReferenceFeed-
backUnit
Setup: All setups
Conversion index: -3
Data type: Int32
Change during operation: True
Enter the analog input scaling value that corresponds to the maximum reference feedback value set in parameter 6-11 Terminal 53
High Voltage and parameter 6-13 Terminal 53 High Current.
Parameter 6-16 Terminal 53 Filter Time Constant
Table 406: Parameter 6-16 Terminal 53 Filter Time Constant
6-16 Terminal 53 Filter Time Constant
Default value: 0.001 s
Parameter type: Range, 0.001 - 10 s
Setup: All setups
Conversion index: -3
Data type: Uint16
Change during operation: True
N O T I C E
This parameter cannot be adjusted while the motor is running.
Enter the filter time constant. This constant is a first-order digital low-pass filter time for suppressing electrical noise in terminal 53. A
high value improves dampening but also increases the delay through the filter.
5.7.3 6-2* Analog Input 2
Parameters for configuring the scaling and limits for analog input 2 (terminal 54).
Parameter 6-20 Terminal 54 Low Voltage
Table 407: Parameter 6-20 Terminal 54 Low Voltage
6-20 Terminal 54 Low Voltage
Default value: Size related
Parameter type: Range, -10.00 - par. 6-21 V
Setup: All setups
Conversion index: -2
Data type: Int16
Change during operation: True
Enter the low voltage value. This analog input scaling value should correspond to the minimum reference value set in parameter
3-02 Minimum Reference.
AU275636650261en-000101 / 130R0334234 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals