N O T I C E
A lower level than default might cause false alarms as it increases sensitivity.
Parameter 14-18 Fast Mains Phase Loss Min Power
Table 715: Parameter 14-18 Fast Mains Phase Loss Min Power
14-18 Fast Mains Phase Loss Min Power
Parameter type: Range, 0 - 100
Change during operation: True
Set the minimum power level (% of nominal power) at which the functions Fast Mains Phase Loss Trip or Fst Mains Phase Loss Warn-
ing (see parameter 14-12 Response to Mains Imbalance) should be activated.
N O T I C E
A minimum power level of 2% is a prerequisite for the Fast Mains Phase Loss function to work.
5.14.3 14-2* Trip Reset
Parameters for configuring auto reset handling, special trip handling, and control card self-test or initialization.
Parameter 14-20 Reset Mode
Table 716: Parameter 14-20 Reset Mode
Default value: [0] Manual reset
Change during operation: True
Select the reset function after tripping. Once reset, the drive can be restarted.
N O T I C E
The motor may start without warning. If the specified number of automatic resets is reached within 10 minutes, the drive enters
[0] Manual reset mode. After the manual reset is performed, the setting of parameter 14-20 Reset Mode returns to the original se-
lection. If the number of automatic resets are not reached within 10 minutes, or when a manual reset is performed, the internal
automatic reset counter returns to 0.
Select [0] Manual reset to perform a reset via [Reset] or via the digital inputs.
Select [1]-[12] Automatic reset x 1… x20 to perform 1–20 automatic resets after tripping.
AU275636650261en-000101 / 130R0334 | 459Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide