Option
Name
Description
[12]
v2 Enabled Always
Enable flying start version 2, at every start.
[13]
v2 Enabled Ref. Dir.
Enable flying start version 2, after coast, search in reference direction only.
[14]
v2 Enab. Alw. Ref. Dir.
Enable flying start version 2, ok at every start, search in reference direction only.
Parameter 1-74 Start Speed [RPM]
Table 125: Parameter 1-74 Start Speed [RPM]
1-74 Start Speed [RPM]
Default value: Size related
Parameter type: Range, 0 - 600 RPM
Setup: All setups
Conversion index: 67
Data type: Uint16
Change during operation: True
Set a motor start speed. After the start signal, the output speed leaps to set value. Set the start function in parameter 1-72 Start
Function to [3] Start speed cw, [4] Horizontal operation, or [5] VVC+ /Flux clockwise, and set a start delay time in parameter 1-71 Start
Delay.
Parameter 1-75 Start Speed [Hz]
Table 126: Parameter 1-75 Start Speed [HZ]
1-75 Start Speed [HZ]
Default value: Size related
Parameter type: Range, 0 - 500.0 Hz
Setup: All setups
Conversion index: -1
Data type: Uint16
Change during operation: True
This parameter can be used for hoist applications (cone rotor). Set a motor start speed. After the start signal, the output speed leaps
to the set value. Set the start function in parameter 1-72 Start Function to [3] Start speed cw, [4] Horizontal operation, or [5] VVC+/Flux
clockwise, and set a start delay time in parameter 1-71 Start Delay.
Parameter 1-76 Start Current
Table 127: Parameter 1-76 Start Current
1-76 Start Current
Default value: 0 A
Parameter type: Range, 0 - par. 1-24 A
Setup: All setups
Conversion index: -2
Data type: Uint32
Change during operation: True
Some motors, for example cone rotor motors, need extra current/starting speed to disengage the rotor. To obtain this boost, set the
required current in parameter 1-76 Start Current. Set parameter 1-74 Start Speed [RPM]. Set parameter 1-72 Start Function to [3] Start
speed cw or [4] Horizontal operation, and set a start delay time in parameter 1-71 Start Delay. This parameter can be used for hoist
applications (cone rotor).
5.2.9 1-8* Stop Adjustments
Parameter 1-80 Function at Stop
Table 128: Parameter 1-80 Function at Stop
1-80 Function at Stop
Default value: [0] Coast
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the drive function after a stop command or after the speed is ramped down to the settings in parameter 1-81 Min Speed for
Function at Stop [RPM].
AU275636650261en-000101 / 130R033498 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals