Parameter 5-24 Terminal X46/9 Digital Input
Table 350: Parameter 5-24 Terminal X46/9 Digital Input
5-24 Terminal X46/9 Digital Input
Default value: [0] No operation
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
The options for this parameter are the same as those listed for parameter 5-20 Terminal X46/1 Digital Input.
Parameter 5-25 Terminal X46/11 Digital Input
Table 351: Parameter 5-25 Terminal X46/11 Digital Input
5-25 Terminal X46/11 Digital Input
Default value: [0] No operation
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
The options for this parameter are the same as those listed for parameter 5-20 Terminal X46/1 Digital Input.
Parameter 5-26 Terminal X46/13 Digital Input
Table 352: Parameter 5-26 Terminal X46/13 Digital Input
5-26 Terminal X46/13 Digital Input
Default value: [0] No operation
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
The options for this parameter are the same as those listed for parameter 5-20 Terminal X46/1 Digital Input.
5.6.3 5-3* Digital Outputs
N O T I C E
The following parameter is only available in FC 302:
Parameter 5-31 Terminal 29 Digital Output
The 2 solid-state digital outputs are common for terminals 27 and 29. Set the I/O function for terminal 27 in parameter 5-01 Terminal
27 Mode, and set the I/O function for terminal 29 in parameter 5-02 Terminal 29 Mode.
N O T I C E
These parameters cannot be adjusted while the motor is running.
Table 353: Digital Outputs, Function Descriptions - 1
Option
Function
[0]
No operation
Default for all digital outputs and relay outputs.
[1]
Control ready
The control card is ready.
[2]
Drive ready
The drive is ready for operation and applies a supply signal on the control card.
[3]
Drive rdy/rem ctrl
The drive is ready for operation and is in auto-on mode.
[4]
Enable/no warning
Ready for operation. No start or stop command has been given (start/disable). No warnings are
active.
[5]
Running
The motor runs, and shaft torque is present.
AU275636650261en-000101 / 130R0334198 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals