Parameter 6-26 Terminal 54 Filter Time Constant
Table 413: Parameter 6-26 Terminal 54 Filter Time Constant
6-26 Terminal 54 Filter Time Constant
Parameter type: Range, 0.001 - 10 s
Change during operation: True
N O T I C E
This parameter cannot be adjusted while the motor is running.
Enter the filter time constant. This is a first-order digital low-pass filter time constant for suppressing electrical noise in terminal 54.
Increasing the value improves dampening but also increases the time delay through the filter.
5.7.4 6-3* Analog Input 3 General Purpose I/O MCB 101
Parameter group for configuring the scale and limits for analog input 3 (X30/11) in VLT® General Purpose I/O MCB 101.
Parameter 6-30 Terminal X30/11 Low Voltage
Table 414: Parameter 6-30 Terminal X30/11 Low Voltage
6-30 Terminal X30/11 Low Voltage
Default value: Size related
Parameter type: Range, -10.00 - par. 6-31 V
Change during operation: True
Sets the analog input scaling value to correspond to the low reference feedback value (set in parameter 6-34 Term. X30/11 Low Ref./
Feedb. Value).
Parameter 6-31 Terminal X30/11 High Voltage
Table 415: Parameter 6-31 Terminal X30/11 High Voltage
6-31 Terminal X30/11 High Voltage
Parameter type: Range, par. 6-30 V - 10 V
Change during operation: True
Sets the analog input scaling value to correspond to the high reference feedback value (set in parameter 6-35 Term. X30/11 High Ref./
Feedb. Value).
Parameter 6-34 Term. X30/11 Low Ref./Feedb. Value
Table 416: Parameter 6-34 Term. X30/11 Low Ref./Feedb. Value
6-34 Term. X30/11 Low Ref./Feedb. Value
Default value: Size related
Parameter type: Range, -999999.999 - 999999.999 ReferenceFeed-
backUnit
Change during operation: True
Sets the analog input scaling value to correspond to the low voltage value (set in parameter 6-30 Terminal X30/11 Low Voltage).
AU275636650261en-000101 / 130R0334236 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide