5.31.5 42-4* SS1
Parameter 42-40 Type
Table 1388: Parameter 42-40 Type
Change during operation: False
Use this parameter to select the type of SS1 safety function.
Parameter 42-41 Ramp Profile
Table 1389: Parameter 42-41 Ramp Profile
Default value: [0] Linear
Change during operation: False
Parameter 42-42 Delay Time
Table 1390: Parameter 42-42 Delay Time
Parameter type: Range, 0.1 - 3600 s
Change during operation: False
Configure the time during which STO must be activated.
Parameter 42-43 Delta T
Table 1391: Parameter 42-43 Delta T
Parameter type: Range, 0 - 99%
Change during operation: False
T subtracts from the time in parameter 42-42 Delay Time to get the motor to stop before the timer expires.
AU275636650261en-000101 / 130R0334 | 673Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302