Parameter 36-44 Terminal X49/7 Bus Ctrl
Table 1334: Parameter 36-44 Terminal X49/7 Bus Ctrl
36-44 Terminal X49/7 Bus Ctrl
Default value: 0%
Parameter type: Range, 0 - 100%
Setup: All setups
Conversion index: 0
Data type: N2
Change during operation: True
This parameter contains the output level of terminal X49/7 if the terminal is controlled by bus.
Parameter 36-45 Terminal X49/7 Timeout Preset
Table 1335: Parameter 36-45 Terminal X49/7 Timeout Preset
36-45 Terminal X49/7 Timeout Preset
Default value: 0%
Parameter type: Range, 0 - 100%
Setup: 1 setup
Conversion index: 0
Data type: Uint16
Change during operation: True
The drive sends the value of this parameter to the output terminal when the terminal is controlled by a fieldbus and a timeout is
detected.
5.29.6 36-5* Output X49/9
Use the parameters in this group to configure the mode of inputs and outputs of VLT® Programmable I/O MCB 115.
N O T I C E
The following parameter is only available in FC 302:
Parameter 36-51 Terminal X49/9 Digital Output.
Parameter 36-50 Terminal X49/9 Analogue Output
Table 1336: Parameter 36-50 Terminal X49/9 Analogue Output
36-50 Terminal X49/9 Analogue Output
Default value: [0] No operation
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the functionality of terminal X49/9.
Option
Name
Description
[0]*
No operation
Indicates no signal on the analog output.
[52]
MCO
[100]
Output frequency
0 Hz = 0 mA; 100 Hz = 20 mA.
[101]
Reference
Parameter 3-00 Reference Range [Min - Max] 0% = 0 mA; 100% = 20 mA
Parameter 3-00 Reference Range [-Max - Max] -100% = 0 mA; 0% = 10 mA; +100% = 20 mA.
[102]
Feedback
[103]
Motor current
The value is taken from parameter 16-37 Inv. Max. Current. The inverter maximum current (160%
current) is equal to 20 mA.
Example: Inverter normal current (11 kW) is 24 A. 160 %=38.4 A. Motor normal current is 22 A, the
readout is 11.46 mA.
AU275636650261en-000101 / 130R0334 | 649Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals