Parameter 30-72 PLM Min. Speed
Table 1090: Parameter 30-72 PLM Min. Speed
30-72 PLM Min. Speed
Default value: 25%
Parameter type: Range, 0 - 100%
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: True
This parameter shows the minimum detection speed above which the PLM algorithm is allowed to act. The speed is given in [%]
relative to parameter 1-25 Motor Nominal Speed.
Parameter 30-73 PLM Detection Factor
Table 1091: Parameter 30-73 PLM Detection Factor
30-73 PLM Detection Factor
Default value: 5
Parameter type: Range, 2 - 100
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: True
This parameter gives a detection sensitivity factor for the PLM feature - a copper loss multiplier. The PLM flags a blocked motor
when the monitored energy throughout the time window is lower than the copper loss energy multiplied by this sensitivity param-
eter.
5.23.5 30-8* Compatibility (I)
N O T I C E
The following parameter is only available in FC 302:
Parameter 30-80 d-axis Inductance
Parameter 30-80 d-axis Inductance (Ld)
Table 1092: Parameter 30-80 d-axis Inductance (Ld)
30-80 d-axis Inductance (Ld)
Default value: Size related
Parameter type: Range, 0.000 - 1000.000 mH
Setup: All setups
Conversion index: -6
Data type: Int32
Change during operation: False
Enter the value of the d-axis inductance. Obtain the value from the permanent magnet motor datasheet. The d-axis inductance
cannot be found by performing an AMA.
Parameter 30-81 Brake Resistor (ohm)
Table 1093: Parameter 30-81 Brake Resistor (ohm)
30-81 Brake Resistor (ohm)
Default value: Size related
Parameter type: Range, 0.01 - 65535.00 ohm
Setup: 1 setup
Conversion index: -2
Data type: Uint32
Change during operation: True
Set the brake resistor value in Ω. This value is used for monitoring the power to the brake resistor in parameter 2-13 Brake Power
Monitoring. This parameter is only active in drives with an integral dynamic brake.
AU275636650261en-000101 / 130R0334 | 583Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals