Parameter 15-20 Historic Log: Event
Table 778: Parameter 15-20 Historic Log: Event
15-20 Historic Log: Event
Default value: 0
Parameter type: Range, 0 - 255, Array [50]
Setup: All setups
Conversion index: 0
Data type: Uint8
Change during operation: False
View the event type of the logged events.
Parameter 15-21 Historic Log: Value
Table 779: Parameter 15-21 Historic Log: Value
15-21 Historic Log: Value
Default value: 0
Parameter type: Range, 0 - 2147483647, Array [50]
Setup: All setups
Conversion index: 0
Data type: Uint32
Change during operation: False
View the value of the logged event. Interpret the event values as below:
Digital input
Decimal value. See parameter 16-60 Digital Input for a description after converting to binary value.
Digital output (not
monitored in this SW re-
lease)
Decimal value. See parameter 16-66 Digital Output [bin] for a description after converting to binary val-
ue.
Warning word
Decimal value. See parameter 16-92 Warning Word for a description.
Alarm word
Decimal value. See parameter 16-90 Alarm Word for a description.
Status word
Decimal value. See parameter 16-03 Status Word for a description after converting to binary value.
Control word
Decimal value. See parameter 16-00 Control Word for a description.
Extended status word
Decimal value. See parameter 16-94 Ext. Status Word for a description.
Parameter 15-22 Historic Log: Time
Table 780: Parameter 15-22 Historic log: Time
15-22 Historic log: Time
Default value: 0 ms
Parameter type: Range, 0 - 2147483647 ms, Array [50]
Setup: All setups
Conversion index: -3
Data type: Uint32
Change during operation: False
View the time at which the logged event occurred. Time is measured in ms since the drive was started. The maximum value corre-
sponds to approximately 24 days, which means that the count restarts at 0 after this period.
5.15.9 15-3* Alarm Log
Parameters in this group are array parameters where up to 10 fault logs can be viewed. 0 is the most recent logged data and 9 is the
oldest. Fault codes, values, and time stamp can be viewed for all logged data.
Parameter 15-30 Fault Log: Error Code
Table 781: Parameter 15-30 Fault Log: Error Code
15-30 Fault Log: Error Code
Default value: 0
Parameter type: Range, 0 - 65535, Array [10]
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: False
AU275636650261en-000101 / 130R0334488 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals