Option
Name
Description
[20]
125 Kbps
[21]
250 Kbps
[22]
500 Kbps
Parameter 10-02 MAC ID
Table 581: Parameter 10-02 MAC ID
10-02 MAC ID
Default value: Size related
Parameter type: Range, [N/A]
Setup: 2 setups
Conversion index: 0
Data type: Uint8
Change during operation: True
Select the station address. Every station connected to the same network must have an unambiguous address.
Parameter 10-05 Readout Transmit Error Counter
Table 582: Parameter 10-05 Readout Transmit Error Counter
10-05 Readout Transmit Error Counter
Default value: 0
Parameter type: Range, 0 - 255
Setup: All setups
Conversion index: 0
Data type: Uint8
Change during operation: True
View the number of CAN control transmission errors since the last power-up.
Parameter 10-06 Readout Receive Error Counter
Table 583: Parameter 10-06 Readout Receive Error Counter
10-06 Readout Receive Error Counter
Default value: 0
Parameter type: Range, 0 - 255
Setup: All setups
Conversion index: 0
Data type: Uint8
Change during operation: True
View the number of CAN control receipt errors since the last power-up.
Parameter 10-07 Readout Bus Off Counter
Table 584: Parameter 10-07 Readout Bus Off Counter
10-07 Readout Bus Off Counter
Default value: 0
Parameter type: Range, 0 - 255
Setup: All setups
Conversion index: 0
Data type: Uint8
Change during operation: True
5.11.2 10-1* DeviceNet
Parameter 10-10 Process Data Type Selection
Table 585: Parameter 10-10 Process Data Type Selection
10-10 Process Data Type Selection
Default value: Size related
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the instance (telegram) for data transmission. The instances available depend on the setting of parameter 8-10 Control Word
Profile. When parameter 8-10 Control Word Profile is set to [0] FC Profile, options [0] INSTANCE 100/150 and [1] INSTANCE 101/151 in this
parameter are available. When parameter 8-10 Control Word Profile is set to [5] ODVA, options [2] INSTANCE 20/70 and [3] INSTANCE
AU275636650261en-000101 / 130R0334328 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals