Parameter 40-29 B-EMF Protection Log Readout
Table 1355: Parameter 40-29 B-EMF Protection Log Readout
40-29 B-EMF Protection Log Readout
Default value: 0
Parameter type: Range, 0 - 65535
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: True
Readout parameter to log events if the Back EMF has been enabled or disabled. The range of the readout parameter is between [0x0
-0xFFFF] hex. The value indicates the bit pattern to identify the current state of Back EMF in the drive. Bit 1 is set: When Back EMF is
enabled, the bit is set to 1. Once enabled the Back EMF cannot be reversed. Bit 1 and bit 2: Motor frequency exceeded Back EMF
limitation. Bit 2 can be reversed. Bit 1, bit 2, and bit 3: The drive has been coasted as motor frequency exceeded the Back EMF limita-
tion. Bit 1, bit 2, bit 3, bit 4: The drive has generated an overvoltage alarm because the drive has coasted as the motor frequency
exceeded Back EMF limitation.
5.30.3 40-4* Extend. Fault Log
Parameters in this group are array parameters, where up to 10 alarm logs can be viewed. [0] is the most recently logged data and [9]
is the oldest. This parameter group provides details on reference, frequency, motor current, voltage, DC-link voltage, status, and
control word values at the time an alarm occurred.
Parameter 40-40 Fault Log: Ext. Reference
Table 1356: Parameter 40-40 Fault Log: Ext. Reference
40-40 Fault Log: Ext. Reference
Default value: 0%
Parameter type: Range, -200 - 200%, Array [10]
Setup: All setups
Conversion index: -1
Data type: Int16
Change during operation: False
View the present reference value applied on impulse or analog basis when the logged event occurred.
Parameter 40-41 Fault Log: Frequency
Table 1357: Parameter 40-41 Fault Log: Frequency
40-41 Fault Log: Frequency
Default value: 0 Hz
Parameter type: Range, 0 - 6500 Hz, Array [10]
Setup: All setups
Conversion index: -1
Data type: Uint16
Change during operation: False
View the actual motor frequency value when the logged event occurred.
Parameter 40-42 Fault Log: Current
Table 1358: Parameter 40-42 Fault Log: Current
40-42 Fault Log: Current
Default value: 0 A
Parameter type: Range, 0 - 10000 A, Array [10]
Setup: All setups
Conversion index: 0
Data type: Int32
Change during operation: False
View the motor current measured when the logged event occurred.
Parameter 40-43 Fault Log: Voltage
Table 1359: Parameter 40-43 Fault Log: Voltage
40-43 Fault Log: Voltage
Default value: 0 V
Parameter type: Range, 0 - 6000 V, Array [10]
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: False
View the motor voltage when the logged event occurred.
AU275636650261en-000101 / 130R0334664 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals