5.9.7 8-8* FC Port Diagnostics
These parameters are used for monitoring the bus communication via the drive RS485 port terminals 68–69.
Parameter 8-80 Bus Message Count
Table 536: Parameter 8-80 Bus Message Count
Parameter type: Range, 0 - 0
Change during operation: True
This parameter shows the number of valid telegrams detected on the bus.
Parameter 8-81 Bus Error Count
Table 537: Parameter 8-81 Bus Error Count
Parameter type: Range, 0 - 0, Array [6]
Change during operation: True
This parameter shows the number of telegrams with faults (for example, CRC fault) detected on the bus.
Parameter 8-82 Slave Messages Rcvd
Table 538: Parameter 8-82 Slave Messages Rcvd
Parameter type: Range, 0 - 0
Change during operation: True
This parameter shows the number of valid telegrams addressed to the slave sent by the drive.
Parameter 8-83 Slave Error Count
Table 539: Parameter 8-83 Slave Error Count
Parameter type: Range, 0 - 0
Change during operation: True
This parameter shows the number of error telegrams which are not executed by the drive.