Option
Name
Description
[233]
In power limit
[234]
PE power off
[246]
Emergency mode was act.
[247]
Emergency mode
[249]
Emcy m. OPR unexpected
[250]
Emcy mode limits
[254]
Testing emcy mode
Parameter 36-42 Terminal X49/7 Min Scale
Table 1332: Parameter 36-42 Terminal X49/7 Min Scale
36-42 Terminal X49/7 Min Scale
Default value: 0%
Parameter type: Range, 0 - 200%
Setup: All setups
Conversion index: -2
Data type: Int16
Change during operation: True
Match the minimum output of terminal X49/7 with a required value. The required value is defined as a percentage of the value
selected in parameter 36-40 Terminal X49/7 Analogue Output. To know more about how this parameter works, see parameter 6-52
Terminal 42 Output Max Scale. The following example describes how the drive uses this parameter. Example:
Parameter 36-03 Terminal X49/7 Mode = [0] Voltage 0–10 V.
Parameter 36-40 Terminal X49/7 Analogue Output = [100] Output frequency.
Parameter 4-19 Max Output Frequency = 200 Hz.
Application requirement: If the output frequency is lower than 20 Hz, the output of terminal X49/7 should be 0 V. To fulfil the exam-
ple requirement, enter 10% in parameter 36-42 Terminal X49/7 Min. Scale.
Parameter 36-43 Terminal X49/7 Max. Scale
Table 1333: Parameter 36-43 Terminal X49/7 Max. Scale
Parameter 36-43 Terminal X49/7 Max. Scale
Default value: 100%
Parameter type: Range, 0 - 200%
Setup: All setups
Conversion index: 0
Data type: Int16
Change during operation: True
Scale the maximum output of terminal X49/7. For example, the scaling is done for the following reasons:
To provide an output value lower than the maximum possible value.
To provide the full signal range using output values lower than a certain limit.
To know more about how this parameter works, see parameter 6-52 Terminal 42 Output Max Scale. Example:
Parameter 36-03 Terminal X49/7 Mode = [0] Voltage 0–10 V
Parameter 36-40 Terminal X49/7 Analogue Output = [100] Output Frequency.
Parameter 4-19 Max Output Frequency = 200 Hz.
Example case 1: 5 V maximum output is required when the output frequency is 200 Hz. Parameter 36-43 Terminal X49/7 Max. Scale x
100% = 200%. Example case 2: 10 V maximum output is required when the output frequency is 150 Hz (75% of the maximum out-
put frequency). Parameter 36-43 Terminal X49/7 Max. Scale = 75%.
AU275636650261en-000101 / 130R0334648 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals