Parameter 0-02 Motor Speed Unit
Table 8: Parameter 0-02 Motor Speed Unit
Change during operation: False
N O T I C E
This parameter cannot be adjusted while the motor is running.
N O T I C E
Changing the motor speed unit resets certain parameters to their initial value. Select the motor speed unit before modifying oth-
er parameters.
The information shown in the display depends on the settings in parameter 0-02 Motor Speed Unit and parameter 0-03 Regional Set-
tings. The default settings of parameter 0-02 Motor Speed Unit and parameter 0-03 Regional Settings depend on the region to which
the drive is supplied.
Select to show motor speed variables and parameters using motor speed (RPM).
Select to show motor speed variables and parameters using output frequency (Hz).
Parameter 0-03 Regional Settings
Table 9: Parameter 0-03 Regional Settings
Default value: [0] International
Change during operation: False
N O T I C E
This parameter cannot be adjusted while the motor is running.
Activate parameter 1-20 Motor Power [kW] for setting the motor power in kW and set the default value
of parameter 1-23 Motor Frequency to 50 Hz.
Activate parameter 1-20 Motor Power [kW] for setting the motor power in hp and set the default value
of parameter 1-23 Motor Frequency to 60 Hz.
AU275636650261en-000101 / 130R033436 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide