5
VFD-V Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-81
10-32 REV Limit of Absolute P2P
a
Factory setting 0
Settings
0: No Limit
1~60000
10-31 and 10-32 are protective parameters. When the settings of 02-01~02-06 /
02-23~02-30 are set to d42 P2P FWD Limit/d 43 REV Limit and it is ON, AC drive will free
stop when it is over the limit.
10-33 P2P Command 0
a
Factory setting 0
Settings
0~50000 (in position control 2 mode)
10-34 P2P Command 1
a
Factory setting 0
Settings
0~50000 (in position control 2 mode)
10-35 P2P Command 2
a
Factory setting 0
Settings
0~50000 (in position control 2 mode)
10-36 P2P Command 3
a
Factory setting 0
Settings
0~50000 (in position control 2 mode)
10-37 P2P Command 4
a
Factory setting 0
Settings
0~50000 (in position control 2 mode)
10-38 P2P Command 5
a
Factory setting 0
Settings
0~50000 (in position control 2 mode)
10-39 P2P Command 6
a
Factory setting 0
Settings
0~50000 (in position control 2 mode)
10-40 P2P Command 7
a
Factory setting 0
Settings
0~50000 (in position control 2 mode)
10-41 P2P Pulse
a
Factory setting 1
Settings
1~20000 (*4 for 10-00)
10-42 P2P mm
a
Factory setting 1
Settings
1~20000